Products XLPE FIRE RATED CABLES SINGLE CORE FLEXIBLE, FIRE RATED POWER CABLE, 0.6/1KV HFS-110-TP

CABLE APPLICATION

Description

2 Hour Fire Rated extra flexible power cables. Supply for essential circuits like mains and other areas


CABLE DESIGN

Conductor
Flexible annealed bare copper conductor wire, based on IEC 60228 and AS/NZS 1125 Class 5 & 6
Insulation
Triple layers Mica tape wrapped
X-HF-110 compound, complies to AS/NZS 3808, colour is natural.
Outer Sheath
HFS-110-TP compound, complies to AS/NZS 3808, colour is red.
Properties
Max service temperature: 110°C
Min. Service Temperature: -40°C
Max. Short Circular Temperature: 250°C (5s)
Bending radius 12 x cable diameter
Extra flexible conductor: Class 5 & 6
Chemical resistance: Good
Oils Resistance: Excellent
Impact Resistance: AS/NZS 3013
Fire resistance: 950°C/2h
Flame Retardant: AS/NZS 3013
UV Resistance
Low Smoke Zero Halogen
AS3103 WS Fire Rating
WS52W

CHARACTERISTICS

Part Number Conductor Cable
Nom. Area mm² Stranding Nom. Insulation Thickness mm Nom. Insulation Dia. mm Nom. Sheath Thickness mm Overall Sheath Dia. Approx. Mass Kg/100m
FFR7135C
10 140/0.30 0.7 7.3 1.4 10.1 16.3
FFR7170C
16 224/0.30 0.7 8.4 1.4 11.2 22.4
FFR19135C
25 346/0.30 0.9 10.2 1.4 13.0 32.1
FFR19153C
35 496/0.30 0.9 11.4 1.4 14.2 42.4
FFR19178C
50 714/0.30 1.0 13.4 1.5 16.4 58.6
FFR19214C
70 358/0.50 1.1 15.6 1.5 18.6 81.4
FFR37178C
95 493/0.50 1.1 17.1 1.6 20.3 100.2
FFR37203C
120 620/0.50 1.2 18.8 1.6 22.0 125.2
FFR37225C
150 770/0.50 1.4 20.9 1.7 24.3 156.5
FFR37252C
185 897/0.50 1.6 23.3 1.8 26.9 186.2
FFR61225C
240 1199/0.50 1.7 27.0 1.9 30.8 248.9
FFR61252C
300 1518/0.50 1.8 28.7 2.0 32.7 307.3
FFR61285C
400 2035/0.50 2.0 32.9 2.1 37.1 402.7
FFR61320C
500 2572/0.50 2.2 36.5 2.2 40.9 501.6
FFR127252C
630 3234/0.50 2.4 41.4 2.4 46.2 629.4
0.6/1kV SINGLE FFR 110