Products XLPE FIRE RATED CABLES SINGLE CORE FIRE RATED,POWER CABLE 0.6/1kV HFS-110-TP

CABLE APPLICATION

Description
Power supply to essential circuits like mains and sub mains and other areas where circuit integrity is essential in the event of the fire, where 2 hour circuit integrity is required.

CABLE DESIGN

Conductor
Stranded Plain Annealed Copper to AS/NZS 1125
Insulation
Mica Glass Tape Flame Barrier X-HF-110
Core Colours: White
Sheath
HFS-110-TP
Colour: Black
AS3103 WS Fire Rating
WS52W
Note
** items can be supplied with compacted conductors to AS/NZS 1125 
** items can be supplied with alternative stranding construction to AS/NZS 1125– 7/19/37/61 strands
** overall dimensions may vary due to compacted conductors

CHARACTERTERISTICS

Part Number Conductor Cable
Nom. Area mm² No. & Dia. of Wires No./mm Nom. Dia. mm Nom. Insulation Thickness mm Nom. Sheath Thickness mm Nom. Overall Dia. mm Approx. Mass Kg/100m
FS7135C
10 7/1.35 4.05 0.7 1.4 10 16.0
FS7170C
16 7/1.70** 4.6 0.7 1.4 11 22.0
FS19135C
25 19/1.35** 6.75 0.9 1.4 13 33.0
FS19153C
35 19/1.53** 7.65 0.9 1.4 14 43.0
FS19178C
50 19/1.78** 8.1 1.0 1.4 15.0 56.0
FS19214C
70 19/2.14** 9.8 1.1 1.4 16.0 77.0
FS37178C
95 37/1.78** 11.4 1.1 1.5 18.0 104.0
FS37203C
120 37/2.03** 13.0 1.2 1.5 20 129.0
FS37225C
150 37/2.25** 14.5 1.4 1.6 22 158.0
FS37252C
185 37/2.52** 16.0 1.6 1.6 24 195.0
FS61225C
240 61/2.25** 18.2 1.7 1.7 27 253.0
FS61252C
300 61/2.52** 20.3 1.8 1.8 29 314.0
FS61285C
400 61/2.85** 23.7 2.0 1.9 33 397.0
FS61320C
500 61/3.20** 26.2 2.2 2.0 36 497.0
0.6/1kV SINGLE FS 110