Products XLPE FIRE RATED CABLES SINGLE CORE FIRE RATED,POWER CABLE 0.6/1kV HFS-110-TP
CABLE APPLICATION
Description
Power supply to essential circuits like mains and sub mains and other areas where circuit integrity is essential in the event of the fire, where 2 hour circuit integrity is required.
CABLE DESIGN
Conductor
Stranded Plain Annealed Copper to AS/NZS 1125
Insulation
Mica Glass Tape Flame Barrier X-HF-110
Core Colours: White
Core Colours: White
Sheath
HFS-110-TP
Colour: Black
Colour: Black
AS3103 WS Fire Rating
WS52W
Note
** items can be supplied with compacted conductors to AS/NZS 1125
** items can be supplied with alternative stranding construction to AS/NZS 1125– 7/19/37/61 strands
** overall dimensions may vary due to compacted conductors
** items can be supplied with alternative stranding construction to AS/NZS 1125– 7/19/37/61 strands
** overall dimensions may vary due to compacted conductors
CHARACTERTERISTICS
Part Number | Conductor | Cable | |||||
---|---|---|---|---|---|---|---|
Nom. Area mm² | No. & Dia. of Wires No./mm | Nom. Dia. mm | Nom. Insulation Thickness mm | Nom. Sheath Thickness mm | Nom. Overall Dia. mm | Approx. Mass Kg/100m | |
FS7135C
|
10 | 7/1.35 | 4.05 | 0.7 | 1.4 | 10 | 16.0 |
FS7170C
|
16 | 7/1.70** | 4.6 | 0.7 | 1.4 | 11 | 22.0 |
FS19135C
|
25 | 19/1.35** | 6.75 | 0.9 | 1.4 | 13 | 33.0 |
FS19153C
|
35 | 19/1.53** | 7.65 | 0.9 | 1.4 | 14 | 43.0 |
FS19178C
|
50 | 19/1.78** | 8.1 | 1.0 | 1.4 | 15.0 | 56.0 |
FS19214C
|
70 | 19/2.14** | 9.8 | 1.1 | 1.4 | 16.0 | 77.0 |
FS37178C
|
95 | 37/1.78** | 11.4 | 1.1 | 1.5 | 18.0 | 104.0 |
FS37203C
|
120 | 37/2.03** | 13.0 | 1.2 | 1.5 | 20 | 129.0 |
FS37225C
|
150 | 37/2.25** | 14.5 | 1.4 | 1.6 | 22 | 158.0 |
FS37252C
|
185 | 37/2.52** | 16.0 | 1.6 | 1.6 | 24 | 195.0 |
FS61225C
|
240 | 61/2.25** | 18.2 | 1.7 | 1.7 | 27 | 253.0 |
FS61252C
|
300 | 61/2.52** | 20.3 | 1.8 | 1.8 | 29 | 314.0 |
FS61285C
|
400 | 61/2.85** | 23.7 | 2.0 | 1.9 | 33 | 397.0 |
FS61320C
|
500 | 61/3.20** | 26.2 | 2.2 | 2.0 | 36 | 497.0 |
0.6/1kV SINGLE FS 110